WATER LEAK DETECTION EQUIPMENT
The WLDS-10 mk3 & WLDS-20 mk3 BREEAM WAT03 water leak detection systems monitor the flow of water into a building. If the flow rate exceeds preset parameters an alarm sounds and optionally the water supply can be shut off.
WLDS water leak detection systems activate when the flow of water exceeds the preset maximum for the preset period of time. It can identify different flows and therefore leakage rates, in accordance with BREEAM WAT03. These parameters can be adjusted by the user to allow for different conditions.
IMPORTANT: in order that meaningful parameters are entered, a full water audit should be carried out to establish water consumption trends over a period of time.
WLDS-10 & WLDS-20 mk3 BREEAM WATER LEAK DETECTION SYSTEMS
Designed to detect major water leaks and help prevent flood damage caused by leaking pipes and fittings or by vandalism.
The WLDS-10 mk3 water leak detector panel is connected to a pulse water meter installed at the site boundary or main water intake point of the building to monitor the consumption of water. An audible/visual alarm output is activated when a continuous flow of water passes through the water meter at a flow rate above a preset maximum for a preset period of time.
A Normally Open free contact is provided for connection to a BMS (Building Management System) or to activate a local sounder/beacon type alarm – see accessories below.
A free contact is also provided to shut off the water supply via a solenoid shut off valve if required. This contact may be programmed to suit a Normally Closed or a Normally Open solenoid valve as required.
The WLDS-20 mk3 is for installations where a pulse water meter is installed at the site boundary and at the main intake point of the building and in addition can detect a loss of water between the site boundary and the main intake point.
ACCESSORIES: SB-100 24v DC Sounder Beacon, can be hardwired locally or elsewhere in the building, programmable sound and volume. WMB-100 set of 4 steel wall mounting brackets, these enable the panel to be wall mounted using screws or bolts external to the panel.
NEW WLDS-10 & WLDS-20 MK3 FEATURES FROM APRIL 2018 MAKING OUR LEAK ALARM SYSTEM EVEN BETTER!
SOLENOID VALVE SETUP: Enables a Normally Closed or a Normally Open solenoid valve to be selected in software. Also a timed valve service function can be set to reduce the likelihood of valve sticking due to calcification etc.
EXTERNAL ALARM INPUT: This input is available for the connection of ancillary equipment such as tape leak sensing to be interfaced to the water leak detection system.
ENCLOSURE: slightly larger at 300 x 300 x 150mm with a RH hinged door. This facilitates easier wall mounting and access to the internal terminals.
FOR SPECIAL APPLICATIONS: please contact our sales department
Leak Alarm System Specifications:
Power requirements: Universal input 100-260v AC 50/60Hz 1.5A maxPulse Meter Input: 24v DC 5mA maximum for reed switch type pulse meter, programmable for 1, 5, 10 or 100 litres per pulse
PSU Output: 24v DC @ 1.1A for powering alarm or solenoid valves
Alarm Output: Normally open free relay contact rated at 5A resistive load 250v AC / 30v DC
Valve Output: Free relay contact rated at 5A resistive load 250v AC / 30v DC, programmable as Normally Open or Normally Closed with timed service function Additional outputs: two alarm contacts are available
External HF/LF input: overrides internal clock
External alarm input: enable ancillary equipment such as tape sensing to be interfaced to the WLDS-10/20 mk3 panels
LCD display: 2x 16 ASCII character with LED backlight
Keypad: with tactile feedback 0-9 numeric keys plus navigation keys for parameter setting and monitoring
Parameters: Litres input range 1 – 32,767, time input range 1 minute – 45 hours, number of High Alerts to alarm: 1-99
Real Time clock: displaying day and time (24Hr format) with automatic GMT/BST changeover. Battery backed (10 year life).
Connections: via DIN rail terminals, maximum conductor size 4mm², cable entry via stuffing glands in gland plate
Enclosure: IP65, steel wall mounting overall dimensions 300 x 300 x 150mm (W x H x D) RAL7035 powder coated
Overall weight of leak alarm system: Approximately 6Kg
FEATURES OF OUR WATER LEAK DETECTION EQUIPMENT
- Easy to navigate user interface
- Accepts inputs from 1, 5, 10 or 100 LPP reed switch type pulse meters
- Main (M1) & Sub (M2) pulse meters can have different K factors
- 7 day clock enables different periods of high flow (HF) to be programmed
- Peak flow capture enables easy setting of accurate parameters
- Displays total throughput in litres – useful for parameter setting and Water Audits
- Output contact for BMS or optional SB-100 sounder/beacon alarm
- Output for 24v DC N. Closed or N. Open solenoid valve with timed service function
- Manual override (protection off) function with adjustable timeout period
- Alarm test function
- Tough steel wall mounting enclosure to IP65 protection, optional wall mounting brackets WMB-100
- Universal 100-240v 50/60Hz input for Worldwide use
- Other features and options available upon request
- Water leak alarm system is manufactured in the UK
OPTIONAL EXTRAS
SB-100
24v DC Sounder Beacon. An optional extra for the WLDS-10 & 20 leak detection panel
WMB-100
Steel wall mounting bracket kit for WLDS Leak Detection Panels